DL3000-ASM
ASCII Serial Interface
Note: The DL3000-ASM has now been replaced by the DL3500-DH+/ASCII.
The newest DataLink DL3000-ASM is an amalgamation of two existing products: the DL3000-ASM and the DL3000-ASC. The improved compact freestanding ASCII serial interface gives customers the ability to send as well as receive ASCII messages via A-B Data Highway Plus.
The DataLink DL3000-ASM facilitates ASCII data transfer to any PLC including models without an ASCII port, such as A-B’s ControlLogix.
A block of data is temporarily stored in the ASM’s 240-byte buffer until the buffer is filled or an ASCII carriage return is detected in the data. Once the data is terminated, the bytes are transmitted to the PLC's integer files in DH+ protocol format. All bytes are retransmitted in the order they were received minus the carriage return.
The DL3000-ASM now has the added functionality of the DL3000-ASC, enabling ASCII messages stored in PLC-5 data tables to be transferred over DH+ to a serial printer or message display.
The -ASM is specifically designed to buffer DH+ message commands sent to its station address from any PLC-5. The transmitted ASCII bytes are then flipped to produce messages on the printer in the same order as the ASCII data is entered and displayed in the PLC.
Features:
Flexible System Layout: scanners, printers, and message displays located anywhere on a DH+ network can send and receive ASCII messages to and from PLCs in other locations
Compact and Lightweight: Small footprint for installation convenience
Easy Configuration: All parameters are menu-driven
High Speed: Serial speeds from 300 baud to 19.2 Kbaud and also 57.6 Kbaud
Specifications:
Interfaces
Channel A: Synchronous; SDLC Transformer-coupled
Channel B: Asynchronous; RS232C/RS422/RS485
Physical Dimensions
Size: 7.5" D x 5.5" W x 1.5" H
(190mm x 140mmx 38mm)
Weight: 2.2lbs (1kg.)
Power
AC: 110/220 VAC (+/- 25%); 50/60 Hz; 5 Watts
DC: 10 - 35 VDC; 5 Watts
Installation
Freestanding; Metal enclosure
Environment
Operating: +32°F to 122°F (0°C to +50°C)
Storage: -40°F to +185°F (-40°C to +85°C)
Humidity: 5% to 95% non-condensing
Protocols
Channel A: Allen-Bradley Data Highway Plus
Channel B: Allen-Bradley DF1 (ANSI X 3.28); Custom
Configuration
PC program software menu for communications parameters |
Selection
Jumpers select supply voltage and
serial interface type
Indicators
1 LED for power-on; 5 LEDs for communications activity
Switches
Reset and Configure/Diagnostics mode pushbuttons
Error Detection
Channel A: CRC
Channel B: BCC or CRC
Communications
Channel A: Synchronous, DH+ at
57.6 Kbaud
Channel B: Asynchronous; 300 baud to
19.2 Kbaud;
High-speed 57.6 Kbaud selection
Hardware
Z180 Processor; 32 Kbyte Flash-PROM;
8 Kbyte RAM; 32 byte EEPROM;
1 DH+ and 2 serial interface connectors |
|
|