DL-PC
ISA Bus Card Interfaces PCs to Allen-Bradley (AB) Networks
DL-PC Documentation
Interface Cards User Guide (pdf)
Interface Cards Quick Start (pdf)
DL-PC RIO Application Note (pdf)
DF1 Converter to AB
Ascii Converter to DH
DL-PC
ISA Bus Card Interfaces PCs to AB Networks

The DataLink DL-PC (DL) is an ISA bus pc card that enables Computers, PCs and OEM equipment to connect to Allen-Bradley networks at high-speed. The DL can be configured as either a station on Data Highway Plus or as one or more adapters (virtual racks) on Remote I/O.

Highlights:

  • Less expensive alternative to A-B 1784-KT(X)
  • Fastest pc interface to DH+ and RIO.
  • Runs existing A-B serial protocols at bus speeds.
  • A-B network speeds up to 230.4 KB.
  • In-place menu configuration; no jumpers to set.
  • Built-in firmware; operates independent of PC.
  • Card includes DH+ & RIO (adapter) protocols.
  • 1 year warranty & 30 day money-back guarantee

DL's interface to ISA bus using the same COM port emulator as an internal modem card. The built-in COM port front-end buffers the byte data in RAM memory, converts it to serial and then transmits it directly to DH+ or RIO at full network speeds.

The DL's built-in CPU, RAM, and operating firmware in socketted EPROM frees-up valuable computer memory and system resources for use by the application. This unique approach enables ISA bus computers to connect to A-B networks at high speeds using standad communications software. The actual system throughput will depend on CPU, clock speed, application software, A-B network speed and traffic etc.


The DL enables existing A-B DF1 serial drivers, ie. drivers for PLC Channel 0, 1770-KF2 or 1785-KE, to be used with Operating Systems including DOS, Unix & Windows, in applications such as Operator Interfaces, PLC Programming, SCADA and Data Acquisition.

In adapter mode the DL can be configured for 1 to 8 (virtual) racks. A computer can read all the I/O image data on RIO, write a maximum 1024 bits and read/write 64 data blocks of up to 64 words each.


Specifications:

Interfaces
A-B Channel: Synchronous; SDLC Transformer-coupled – DH+
Interface Ethernet Channel: 10 Base-T – Modbus TCP/IP

Physical Dimensions
Size: 1.05" H x 4.2" D x 3.45" W (26.2mm x 105.0mm x 86.3mm)
Weight: 0.66lbs (0.3kg)
Power: 9-27 VDC; Less than 2 Watts

Installation
Metal enclosure; Freestanding or DIN rail mounting clips

Environment
Operating: +32 F to 122 F (0 C to +50 C)
Storage: -40 F to +185 F (-40 C to +85 C)
Humidity: 5% to 95% non-condensing

Protocols
A-B Channel: Allen-Bradley Data Highway Plus or Remote I/O
Ethernet Channel: Modbus TCP/IP – 10 Base T

Configuration
Telnet to IP address for configuring communications parameters.

Indicators
Ethernet - Bi-Color for Modbus TCP/IP activity
A-B Network - Bi-Color for A-B Channel operation
Status - Bi-Color for DL4500 Status
Power - Green for power-on

Tx/Rx – Flashing Green for Modbus TC/IP activity
Diagnostic - Red for Diagnostics
Link - Green for Network Link Status

Pushbuttons
Reset and Configure mode pushbuttons

Communications
A-B Channel: Synchronous, DH+ at 57.6, 115.2, and 230.4 Kbaud
Ethernet Channel: 10 Base–T; Modbus TCP/IP

Hardware
3-pin Phoenix type for A-B DH+
DB9F for Hardware Configuration port
2-pin Phoenix type power connectors
RJ45 type- 10 Base-T Ethernet Connector


Technical Sales
   
 
Call or email for any technical support issues or pricing inquiries

Toll free 1-(866)-286-2745

or

(604) 632-4278
(9:00am EST)
 
     
Our Guarantee
 
Satisfaction Guaranteed.

Your complete satisfaction with all our products is essential.

We offer a 30-day money-back guarantee and a five-year warranty on parts and service.
 
Connect PC / Laptop to AB DH+ / DH-485
Protocol Converter to Modbus
copyright 2006
privacy policy
info@abgateways.com            (604) 632-4278